ICARELIFE · Power, Control & Utilities

OR Digital Clock with Temperature & Humidity Display

A flush-mount LED panel that puts time, date, room temperature and relative humidity on the operating-room wall in one sealed, cleanable unit.

Swiss Sensirion SHT-series sensing gives ±0.3 °C and ±3% RH at the point of care, and an on-board SD card logs both continuously for commissioning records and environment audits. The 500 × 300 × 55 mm aluminium frame is pre-dimensioned for flush integration into ICARELIFE modular operating-room wall panels.

Swiss Sensirion SHT sensor ±0.3 °C · ±3% RH SD card data logging
View specifications →
ICARELIFE OR digital clock displaying time, date, temperature and humidity on an operating room wall
Panel size500 × 300 × 55 mm
Accuracy±0.3 °C · ±3% RH
DisplayTime, date, T & RH
PowerAC 220 V / ≤80 W

Product range

OR Digital Clock

One display unit, three mounting options: flush-embedded in an ICARELIFE modular wall panel, surface-mounted on a finished wall, or ceiling-suspended. Custom panel sizes are built to order.

Flush-mounted OR digital clock with temperature and humidity display
ORC-500FOR Digital Clock · Flush-MountEnvironment display · Recessed in OR wall panels500 × 300 × 55 mmFlush-embedded panel for modular operating-room wall systems. Needs a 500 × 300 mm cutout and at least 60 mm cavity depth.
OR digital clock with temperature and humidity display, surface mounting option
ORC-500SOR Digital Clock · Surface / Ceiling MountEnvironment display · Surface or suspended500 × 300 × 55 mmSame panel on a surface bracket or ceiling suspension, for refurbishments and theatres where the wall zone is already occupied.

Construction & specifications

Four parameters, one sealed wall panel

The unit consolidates time, date, temperature and relative humidity into a single flush panel, so the surgical team reads the room environment from anywhere in the theatre without a separate instrument cluster. An anodised aluminium alloy frame carries a black acrylic front; high-brightness red LED digit segments stay legible under full operating-theatre lighting. Sensing is handled by a factory-calibrated Swiss Sensirion SHT-series element — the same platform trusted in pharmaceutical and semiconductor cleanrooms — and every reading is written continuously to an on-board SD card. Because the panel is pre-dimensioned at 500 × 300 mm, it drops into the same modular operating-room wall system as the control panel and the gas terminal boxes, so there is no separate procurement and no dimensional mismatch on site.

SpecificationDetail
Dimensions & build500 × 300 × 55 mm (W × H × D); anodised aluminium alloy frame with a black acrylic front panel; high-brightness red LED digit display
Temperature & humidity sensingSwiss Sensirion SHT-series sensor, factory calibrated; temperature −9 °C to +60 °C at ±0.3 °C (25 °C reference); relative humidity 0–100% at ±3% RH (25 °C, 50% RH reference); display unit switchable between °C and °F
Display content & loggingTime HH:MM:SS (24 h), date YYYY/MM/DD, temperature and relative humidity shown simultaneously; continuous temperature and humidity logging to an on-board SD card slot
Electrical & controlAC 220 V / 50 Hz, ≤80 W; 1.5 m cable exiting the top of the unit; brightness, date/time and units set by push-button or infrared remote control

Mounting

Three ways to install the same panel

Mounting is selected at order stage, because it changes the cutout detail, the bracket set and the way the cable is brought to the unit.

OptionTypical applicationWhat to coordinate
Flush-wall (recessed)Modular OR wall panel systems; the default for new theatre builds500 × 300 mm cutout and at least 60 mm cavity depth; cutout position fixed before panel fabrication
Surface-wallRefurbishment over a finished wall, or where cavity depth is limited55 mm projection from the finished surface; cable route to the top of the unit
Ceiling-suspendedTheatres where the wall zone is fully occupied by equipmentSuspension bracket and drop height; viewing angle from the operating table
Measuring status: this panel displays and logs room conditions; it is not a certified medical measuring instrument and it has no alarm output. Where a regulated environment requires traceable calibrated monitoring, run a certified data logger in parallel and take out-of-limit alerts from the BMS or room controller.

Applications

Where the panel is specified

Specified on hospital and life-science projects in Southeast Asia, the Middle East, Europe and South America wherever a controlled space needs continuous, staff-visible environment data.

Operating roomGives the surgical team real-time temperature and humidity against the ASHRAE 170 targets of 20–24 °C and 20–60% RH.
CleanroomSupports ISO 14644 environment monitoring in pharmaceutical, electronics and medical-device manufacturing.
ICU & isolation roomContinuous staff-accessible readouts for intensive care and negative-pressure isolation rooms.
Pharmacy & sterile compoundingDisplays conditions in controlled compounding areas run to GMP EU Annex 1 and USP <797>.
LaboratoryAmbient conditions where temperature or humidity affect test validity and equipment calibration.
CSSD / sterile servicesMonitoring in central sterile supply departments where conditions affect sterilisation integrity.

Standards & reference guidelines

What the readings are checked against

The panel displays and logs environment data. The targets themselves are delivered by the HVAC and AHU system — these are the references the readings are normally measured against.

ReferenceScopeTargets / relevance
ASHRAE 170Ventilation of Health Care FacilitiesOperating room temperature 20–24 °C, relative humidity 20–60% RH
ISO 14644-1 / -2Cleanroom classification & monitoringTemperature and humidity are monitored parameters; SD card logging supports the records ISO 14644-2 requires
HTM 03-01UK NHS healthcare ventilationOperating room temperature 18–25 °C, relative humidity 40–60% RH
GMP EU Annex 1Manufacture of sterile medicinal productsDocumented environmental monitoring in sterile manufacturing and pharmacy compounding; the SD log supports the audit trail
Project coordination: Fix the rough opening at design stage: the panel needs a 500 × 300 mm cutout, and the 55 mm body needs at least 60 mm of cavity or sub-frame depth behind the wall finish. The cable leaves the top of the unit, so conduit routing has to be coordinated with the MEP package before the wall panels are fabricated.

How to specify

How to specify your OR digital clock

MountingFlush-wall (recessed), surface-wall or ceiling-suspended — nominate at order stage
Panel sizeStandard 500 × 300 × 55 mm; custom sizes on request, about 10 working days extra
Display units°C or °F, selectable by push-button or infrared remote
Power & cablingAC 220 V / 50 Hz, ≤80 W; 1.5 m cable from the top of the unit
Data & alarmsOn-board SD logging standard; no alarm output — out-of-limit alerts sit with the BMS or room controller
DocumentationDatasheet, dimensional drawing, Sensirion calibration reference and specification letter for tender packages

FAQ

Frequently asked questions

No. The standard unit is display-only: it shows current time, date, temperature and relative humidity, but it has no audible or visual out-of-limit alert. Out-of-limit alarms are handled by the building management system or a dedicated environment monitoring system connected to the AHU or room controller. Tell us at enquiry stage if your project needs an alarm-enabled variant and we will price it as a separate line item.

No. It is a display and logging device, not a certified medical measuring instrument. The Sensirion SHT-series element is factory calibrated to ±0.3 °C and ±3% RH and ICARELIFE supplies the calibration reference with the unit, but where a regulatory regime requires traceable calibrated monitoring you still need a certified data logger running in parallel. The SD card log suits internal record-keeping and commissioning documentation, not statutory calibration records.

Usually yes. Flush installation needs a 500 × 300 mm cutout and at least 60 mm of cavity or sub-frame depth behind the finish; where the cavity is too shallow the panel can be surface-mounted instead, projecting 55 mm from the wall. Send us the wall build-up and a photograph of the current installation and we will confirm the fit before you order.

The on-board SD card records temperature and humidity continuously — remove the card or connect it to a PC to read the log. There is no network or BMS output on the standard unit, so if your project needs readings fed into the hospital BMS, the AHU or room-controller sensors are the normal source. We coordinate that interface during design.

Standard lead time is 20–30 working days from order confirmation and deposit for the 500 × 300 mm panel; custom sizes add about 10 working days. There is no fixed minimum order — single units are accepted on a project basis — and batch deliveries can be scheduled against the site programme.

ICARELIFE provides a datasheet, dimensional drawing, installation notes, the Sensirion sensor calibration reference and a technical specification letter on request — the package typically required for government hospital tenders in Southeast Asia, the Middle East and Africa. Request it with your enquiry.

Request a Specification for Your Theatre

Send the mounting option, panel size and wall build-up for a line-item quotation, dimensional drawing and tender documentation pack.

Or contact us directly: info@icarelife.com · WhatsApp · +86 135 7086 7738

Document revision 2026-09

Contact Us

ICARELIFE , Your reliable partner in MOT equipment and supplies.

Ceiling Laminar Airflow

Contact US

ICARELIFE are committed to offering  a wide range of  product for OR builder

Corian Medical Scrub Sink
ICARELIFE, Solution for OR Builder
You reliable solution on modular operating room equipment and supplies.

Contac Us

Contac us

Operating Room Hermetic Door